MISCELLANEOUS | 11/4/2024 | CHELSEY GONZALES |
(11/14/2024 11:07 AM CGO)
Hi Mayra,
Here are the comments the inspector made at time of inspection for Building 21: AS BUILTS & CALCS: Plans indicate a rise up of 2.5 inch steel pipe, 1.25 inch was installed in the field. Plans indicate TY2234 sprinkler heads in legend, TY2236 was installed. Calcs needed due to change in pipe size. Building 21, Plan A.
As-builts will need to be submitted. You can submit them on our website at https://fire.ci.oceanside.ca.us/department-overview/divisions/community-risk-reduction/plan-submittal. Click on the resubmittal link.
If you have any questions regarding the comments please contact Randy Hill at 760-435-4321 or you may email him at rhill@oceansideca.org.
Thank you,
Chelsey Gonzales
Oceanside Fire Department
Office: 760-435-4101
300 North Coast Hwy
Oceanside, CA 92054
|
More Info
|
BLUEBEAM SESSION NUMBER | 11/16/2022 | CHELSEY GONZALES |
(11/17/2022 11:53 AM CGO)
898-254-464 2nd Submittal |
More Info
|